Product Description
1.1 Functional Features
1. Test Item:
(1) Voltage Regulation Accuracy Measurement
(2) Measurement of Flow Stability Accuracy
(3) Voltage Regulation Characteristic Experiment
(4) Current-Limiting Characteristic Experiment
(5) Ripple Factor Measurement
(6) Measurement of DC Current Output Error
(7) Measurement of DC Voltage Output Error
(8) Measurement of Charger Power and Efficiency
(9) Power Factor Measurement
(10) Battery Pack Discharge Test
2. The test interface is divided into three sections:
(1) Regulation accuracy measurement, current-limiting characteristic testing, ripple factor measurement, and DC voltage output error measurement
(2) Measurement of current‑regulation accuracy, experiments on pressure‑limiting characteristics, and measurement of DC current output error
(3) Charger power and efficiency measurement, power factor measurement, battery testing
3. Reference Standard:
(1) DL/T 1397-2014 “General Technical Requirements for Test Equipment Used in Power DC Power Supply Systems”
(2) DL/T 724-2021 “Technical Code for Operation and Maintenance of Battery DC Power Supply Devices for Power Systems”
(3) GB/T 19826-2005 “General Technical Specifications and Safety Requirements for DC Power Supply Equipment in Power Engineering”
4. Equipment Structure: The system comprises components such as input voltage regulation, output load, a test host, and an industrial PC, with a compact footprint for easy portability.
5. Utilizing an industrial control computer as the device’s operating unit, it offers rich functionality, an intuitive interface, simple operation, and a large data storage capacity.
6. In accordance with national and industry standards, implement testing functions for voltage stability accuracy and ripple factor, and measure parameters of DC charging equipment, including load current, DC voltage, voltage regulation accuracy, and ripple factor.
7. 10.4-inch color LCD touchscreen with Windows operating system, featuring a fully Chinese graphical user interface that is simple and convenient.
8. Realistically simulates grid input voltage; AC output voltage is continuously adjustable and features automatic constant-voltage regulation.
9. The parameter testing section employs a high-speed data acquisition card with a sampling rate of 150 MHz, featuring over 20 automatic measurement functions and PASS/FAIL checking capabilities, delivering fast processing, high accuracy, and strong anti-interference performance.
10. Equipped with both manual and automatic test modes; in automatic mode, multi-point testing can be performed automatically according to the pre-programmed sequence.
11. Multiple test procedures can be configured, including: charger input voltage points, charger output voltage points, charger output current points, and test load current points.
12. In automatic test mode, the test is performed automatically according to the user-selected procedure.
13. The AC automatic voltage regulator can adjust the charger’s grid‑side input voltage according to test requirements, with a continuously adjustable range of 85%–115% and automatic constant‑voltage control.
14. Test lead interfaces: Both AC input/output and DC output utilize terminal blocks, and the rear end of the test leads is fitted with dedicated quick-connect terminals.
15. Implement the current‑stability accuracy function in accordance with national and industry standards, and test parameters such as charging voltage, load current, current‑regulation accuracy, pulse peak, pulse trough, average voltage, and the limit of output‑voltage ripple.
16. Equipped with protection functions for overheating, overcurrent, overvoltage, reverse polarity, short circuit, phase loss, undervoltage/overvoltage, and overload of the voltage-regulating device; the protection features include manual enable and reset buttons.
17. Upon completion of testing, a test report is automatically generated in Word or Excel format and can be directly saved to a USB flash drive.
18. Equipped with an RS-232 interface for remote control and multiple USB data storage ports.
19. The analysis and management software enables device control, displays various data and waveform graphs, and automatically generates, stores, edits, and prints test reports.
1.2 Operating Environment
Environmental indicators
Serial Number Environmental Indicator Indicator Requirements
1. Protection rating ≥ IP30
2 Operating temperature: -10°C to 50°C
3 Relative humidity: 0–95%
4 Operating noise ≤ 85 dB
5 Operating altitude ≤ 3000 meters
1.3 Power Supply
(1) Input voltage: 220 V AC (±20%);
(2) Input frequency: 50 Hz (±2%).
1.4 Technical Specifications
| Parameter item | Parameter value |
| Applicable Voltage Level | DC 110 V, DC 220 V, and other systems |
| Voltage regulation range | ≥±20% |
| Power supply | AC 220V ±15%, frequency 50 Hz |
| Regulator input voltage | Three-phase four-wire, AC 380 V, 50 Hz |
| Regulator output voltage | Three-phase three-wire, AC 380 V ±20%, 50 Hz |
| Regulator output capacity | 15 kVA ±0.1% |
| Three-phase current detection range | 25A |
| Regulator adjustment method | Automatic software adjustment |
| DC voltage adjustment range | 0-400V |
| DC load current adjustment range | 0–50 A; external DC load testing available for higher capacities. |
| Voltage measurement accuracy | ≤±0.2% |
| Current measurement accuracy | ≤±0.2% |
| RMS measurement accuracy of the ripple factor | ≤±0.1% |
| Peak measurement accuracy of the ripple factor | ≤±0.2% |
| Applicable to the voltage rating of the charger | 110V, 220V |
| Data interface method | USB and RS-232 |
| Optional Features | It supports external battery monitoring, enabling individual cell voltage measurement and allowing users to set alarm and termination voltages based on each cell’s voltage, thereby triggering automatic shutdown of the device; it provides single-cell monitoring for 2 V, 6 V, and 12 V batteries. |
| Continuous working hours | ≥12h |
| Alternating current power | 1% |
| Ripple measurement time | 0.2%, with a range of 1% |
| Operating method | Touch screen |
| Dimensions (L×W×H) mm | Host: 240×460×480 mm, weight: approximately 21 kg; Voltage regulator: 260×260×710 mm, weight: approximately 30 kg. |
1.5 Configuration List
| Serial number | Name | Unit | Quantity | Note |
| 1 | DC System Charger Characteristic Tester | set | 1 | |
| 2 | Test software package (including communication cable, software installation package, etc.) | set | 1 | A set |
| 3 | Test Accessories Kit | set | 1 | A set of auxiliary accessories, including wire clamps and pins. |
| 4 | Instruction manual, factory test report | set | 1 | A set |
| 6 | Aluminum alloy packaging box | Taiwan | 1 | A set |
Online Inquiry